Hochiki DCP-CZM Conventional Zone Module

Categories: ,

Description

Features & Specifications

 

– UL 864 9th Edition Listed

– Provides an address point for a zone of up to 25 conventional smoke detectors

– Blinks green when polled. Latched on red (controlled by panel) when activated

– Device address can be programmed with a handheld programmer. Device address- ranges from 1 to 127

– Compatible with Class B and Class A wiring

 

Supply Voltage (S-SC): 25.3 ~ 39 VDC
Auxiliary Supply Voltage: 18.8 ~ 27.2 VDC
Average Current Consumption: 670µA
2-Wire Detector Loop Current: 1mA Max.
From Auxiliary Supply: 60mA Max.
EOL Device: 4.7 ohms Resistor
Max. Quantity Per Loop: 127
Alarm Threshold Level:

Wiring Threshold Level: >2.5K ohms &

Open Circuit Threshold Level: >10K ohms